Meiden – 36 & 72.5kV Dry Air Insulated VCB

Features

• No Usage of SF6 Gas
   Pressurized dry air is employed as insulating medium

  • Long Operation Life

   Without inspection of main contacts, VCB is capable of:
    – 10 000 rated current breaking
    – 20 Full fault current breaking
  • Easier Maintenance than GCB

   Vacuum interrupter has self arc extinguishing characteristics
  • Superior Performance in Cold Region

   Applicable ambient temperature without tank heater: -50~40°C

Specifications 36kV

Type designationNVBOA-30732B
Applicable standardsIEC-62271-100 (2008)
Rated voltage (kV)36
Rated current (A)2000
Rated frequency (Hz)50 / 60
Insulation level1 min. power frequency (kV ms)70
1.2 x 50µs impulse (kV peak)200
Rated short time withstand current (kA-sec)31.5-3
Rated peak withstand current (kA peak)82
Dry air pressureRated pressure (MPa)0.50
Low pressure alarm (MPa)0.45
Low pressure lockout (MPa)0.40
Rated operating sequenceOpen – 0.3 sec -Close Open – 3 min – Close Open
Mass without CTs (kg)1500

Specifications 72.5kV

Type designationNVBOA-60732BNVBOA-60740B
Applicable standardsANSI c37.06, IEC 62271-100
Rated voltage (kV)72.5
Rated current (A)2000
Rated frequency (Hz)50 / 60
Insulation level1 min. power frequency (kV ms)160
1.2 x 50µs impulse (kV peak)350
Rated short time withstand current (kA-sec)31.5-340-3
Rated peak withstand current (kA peak)82108
Dry air pressureRated pressure (MPa)0.50
Low pressure alarm (MPa)0.45
Low pressure lockout (MPa)0.40
Rated operating sequenceOpen – 0.3 sec -Close Open – 3 min – Close Open
Mass without CTs (kg)1900